Kelvin vs two-wire shunt current measurement
10 parts
One 100µΩ shunt carries 100A pulses: Kelvin sense wires read 10mV, exactly I·R. Watch the two-wire reading, taken at the bolts over a shared return: 15mV, 50% high. A 48V battery's − terminal is the AFE's ground. The load current returns from P- through lug B (10µΩ), the shunt Rsh (100µΩ), lug A (10 µΩ) and the B- cable (30µΩ) to that terminal, so the two-wire reading shares the cable with the load. The load is an I source pulsing 0/100A at 0.5Hz. Kelvin: ΔV across the shunt's own sense pads, S+ and S-. Two-wire: ΔV from the AFE ground to P-, the far bolt. The ƒx probe, I(Rsh) × 100µΩ, is the true I·R. Press Run: on screen at ×0.25 a pulse comes every 1.6s, and the readings stand while it lasts.
- battery 48V
- load 100A·500mHz
- B- cable 30µΩ
- lug A 10µΩ
- Rsh 100µΩ
- lug B 10µΩ